Fault-loop max length calculator

Maximum circuit length for B, C and D curve breakers.

Fault-loop maximum length

Maximum circuit length
51.1 m
With a 90% design margin
46 m

Method

  • Lmax = 0.8 × Uo × Sph × Spe ÷ (ρ × Ia × (Sph + Spe))
  • Uo = 230 V, ρ = 0.0225 Ω·mm²/m, Ia = 10 × 20 A (C curve)
  • Sph = 2.5 mm², Spe = 2.5 mm² (earth in standard TPS / multicore)

Reference

  • AS/NZS 3000 Appendix B, Table B1 method (0.4 s disconnection)

Notes

  • Assumes the earth size in standard cable shown above. Test Zs at the far end of the circuit.

Verify against the current standard before relying on this.