Smoke alarm certificate
12 Example Street, Southport QLD 4215
SA-0015 · New lease or renewal · Queensland · checked 8 October 2026
Based on the alarms recorded and tested by Sam Sparky on 8 October 2026, they met the Queensland smoke alarm requirements listed below.
- Storeys
- 1
- Bedrooms
- 3
- Hallways and exit paths
- Confirmed covered by the person checking
- Checked by
- Sam Sparky
- Business
- Example Electrical
- Electrical licence
- 00000
- Contact
- 0400 000 000 · hello@example.com
- Next check due
- 8 October 2027 (and within 30 days before any new or renewed lease)
Alarms (5)
1. Bedroom 1
Hardwired (with backup battery) · Photoelectric Yes · AS 3786 Yes · Interconnected Yes
Test: Pass · Tested and cleaned · Replace by 2034-06
2. Bedroom 2
Hardwired (with backup battery) · Photoelectric Yes · AS 3786 Yes · Interconnected Yes
Test: Pass · Tested and cleaned · Replace by 2034-06
3. Bedroom 3
Hardwired (with backup battery) · Photoelectric Yes · AS 3786 Yes · Interconnected Yes
Test: Pass · Tested and cleaned · Replace by 2034-06
4. Hall outside bedrooms
Hardwired (with backup battery) · Photoelectric Yes · AS 3786 Yes · Interconnected Yes
Test: Pass · Tested and cleaned · Replace by 2034-06
5. Living room
Hardwired (with backup battery) · Photoelectric Yes · AS 3786 Yes · Interconnected Yes
Test: Pass · Battery replaced · Replace by 2031-02
| # | Location | Power | Photoelectric | AS 3786 | Interconnected | Replace by | Test | Done |
|---|---|---|---|---|---|---|---|---|
| 1 | Bedroom 1 | Hardwired (with backup battery) | Yes | Yes | Yes | 2034-06 | Pass | Tested and cleaned |
| 2 | Bedroom 2 | Hardwired (with backup battery) | Yes | Yes | Yes | 2034-06 | Pass | Tested and cleaned |
| 3 | Bedroom 3 | Hardwired (with backup battery) | Yes | Yes | Yes | 2034-06 | Pass | Tested and cleaned |
| 4 | Hall outside bedrooms | Hardwired (with backup battery) | Yes | Yes | Yes | 2034-06 | Pass | Tested and cleaned |
| 5 | Living room | Hardwired (with backup battery) | Yes | Yes | Yes | 2031-02 | Pass | Battery replaced |
Requirements checked: photoelectric alarms to AS 3786-2014 with no ionisation sensor; hardwired or with a 10-year sealed battery; all interconnected; an alarm on every storey and in every bedroom; hallways between the bedrooms and the rest of the home, as confirmed by the person checking; every alarm cleaned as well as tested before the lease; not past the replace-by date shown on the alarm. Each alarm was tested with its test button.
Checked against: Fire Services Act 1990 (Qld) Chapter 4A; Building Fire Safety Regulation 2008 Part 5A.
Not assessed: exact placement (distances from walls, corners, lights, fans, vents and stairs) and the wiring behind the alarms. This records the alarms as found and recorded on the day. Rentals must be tested and cleaned within 30 days before a tenancy starts or renews; tenants test and clean every 12 months.