Supporting record of the tests for the Certificate of Electrical Safety (COES). The official certificate is the one issued through Energy Safe Victoria.
CustomerMs Sam Citizen
Address12 Example Street, Geelong, 3220
Date of test8 October 2026
Contractor licence00000 · Example Electrical
Work tested
Kitchen renovation: new 20 A power circuit, oven circuit and LED downlights. Added RCBOs to the switchboard.
| Circuit | Description | Cable | Protection | IR (MΩ) | Cont. (Ω) | Polarity | Conn. | RCD | EFLI (Ω) |
|---|
| 1 | Kitchen power | 2.5 mm² TPS | 20 A RCBO 30 mA | >200 | 0.42 | ✓ | ✓ | Pass · 18 ms | 0.78 |
| 2 | Lights, living and beds | 1.5 mm² TPS | 10 A RCBO 30 mA | >200 | 0.65 | ✓ | ✓ | Pass · 21 ms | 1.12 |
| 3 | Oven | 6 mm² TPS | 32 A RCBO 30 mA | >200 | 0.18 | ✓ | ✓ | Pass · 16 ms | 0.51 |
IR = insulation resistance · Cont. = earth continuity · Conn. = correct circuit connections · RCD = trip test (and trip time) · EFLI = earth fault-loop impedance (N/A: not required, no socket-outlets)